Home >> Product >>Current Sensor >> FR100R Series Rogowski Coil Sensors
Product Detail

FR100R Series Rogowski Coil Sensors

    FR100R  series Rogowski coil sensor is also called flexible current sensor and current sensor. It is a toroidal coil that is wound evenly over non-ferromagnetic material. It has no hysteresis effect, almost zero phase error, no magnetic saturation, and good linearity. The output signal is the differential of current vs. time. By integrating the output voltage signal, the input current can be truly restored, and its measurement current range can range from milliamperes to millions of amperes. Mainly used for AC leakage current, high current, high harmonic current, complex waveform current, transient inrush current, phase, electric power, power, power factor and other detection. With integrator, easy to integrate into other equipment, such as: electric energy meter field calibrator, multi-function energy meter, oscilloscope, digital multimeter, cable identification instrument, cable fault detector, double clamp grounding resistance tester, double clamp phase voltmeters, digital current recorders, etc., can measure and compare a variety of electrical parameters in an uninterrupted state. 


Collect
Product Model FR100R
Product Introduction

Function

AC leakage current, high current, high harmonic current, complex waveform current, transient impulse current, phase, electric power, power, power factor, etc.

Test Method

Flexible CT: The output signal is the differential of current vs. time. By integrating the output voltage signal, the input current can be truly restored.

Coil Line Thickness Dia.

Φ8mm

Output

only coil output: 100mV/1000A, output of the supporting integrator see the Integraph Parameters Table

Power Supply Voltage

supply integrator voltage

Low Current Indication

have

Accuracy Level

± 1.0% FS (23 °C ± 2 °C, 70% RH or less, the wire is at the center of the coil)

Phase Error

≤1°(50Hz/60Hz;23℃±2℃)

Out Interface

BNC connector (optional audio plug, banana plug, bare wire)

Output Line Length

pliers to adapter 50cm, signal output 2m

Electric Field Interference

hysteresis effect, strong resistance to external electric field interference

Conductor Position

The tested wire is in the center of the coil, position error affects ≤±0.5% FS (1cm away from the port position)

Response Frequency

without integrator: 0.1Hz ~ 10MHz , matched integrator: 0.1Hz ~ 1MHz

Line Voltage

circuit test below AC 1000V

Working Temperature and Humidity

-20℃~50℃;below 80%rh

Storage Temperature and Humidity

-10℃~60℃;below 70%rh

Insulation Strength

AC 2000V/rms (between coil and shuck)

Suitable for Safety Regulations

IEC1010-1, IEC1010-2-032, Pollution Level 2, CAT IV 1000V