Home >> Product >>Ground Resistance Tester >> ES3002 Multifuncional double clamp earth tester
Product Detail

ES3002 Multifuncional double clamp earth tester

    Double clamp multi-function grounding resistance tester is also called double clamp grounding resistance tester. The advanced grounding resistance tester integrates a variety of measurement methods. In addition to the traditional function of ancillary grounding resistance, it also has the unique function of measuring without auxiliary ground. It uses a large LCD gray screen backlight display and microprocessor technology, through the microprocessor control precision 4-wire method, 3-wire method and simple 2-wire method, selection method, double clamp method to measure grounding resistance test. Large-diameter current clamp design, using double jaw measurement technology, without the need to hit the auxiliary ground, without the need to isolate the grounding body and equipment to achieve on-line measurement.Suitable for telecommunications, electricity, meteorology, computer rooms, oil fields, power distribution lines, iron tower transmission lines, gas stations, factory grounding networks, lightning rods and so on. Instrument testing is precise, fast, simple, stable and reliable.

    The double clamp multi-function grounding resistance tester is controlled by the microprocessor and can accurately detect the grounding resistance, soil resistivity, grounding voltage, DC resistance and AC current. It uses a fast filtering technique to minimize interference. The resistance value of the auxiliary electrode is displayed on the same screen to facilitate the determination of the measurement error due to environmental factors, and it is convenient to measure the true grounding resistance more accurately.At the same time store 500 sets of data,online monitoring data through monitoring software, USB data uploaded to PC and unique features such as intelligent alarm alert

    Double clamp multi-function grounding resistance tester consists of host, monitoring software, test line, USB cable, and grounding rod. It has the functions of reading, checking, saving, reporting and printing of historical data.


Collect
Product Model ES3002
Product Introduction

Function

Ground resistance¡¢Soil resistivity¡¢DC resistance¡¢Ground voltage¡¢AC current

Ambient temperature and humidity

23¡æ¡À5¡æ£¬below 75%rh

Interference voltage

<20V (should be avoided)

Interference current

<2A (should be avoided)

Measure R electrode spacing

a£¾5d

Measured ¦Ñelectrode spacing

a£¾20h

Power

8.4V lithium battery (built-in)

Backlight

Controllable  backlight, suitable for use in dim places

measurement mode

Precise four-wire¡¢ three-wire measurement, simple two-wire measurement¡¢Selection method, double clamp method for measuring grounding resistance

Measurement methods

2.3.4-wire method measurement: Polarization method, measuring current 20mA Max

Soil resistivity: four-pole method 

Selectivity Measurement: Polarization Method, Measuring Current 20mA Max

Double clamp method: non-contact mutual inductance measurement method, test current 1mA Max

DC resistance: polarization method

AC current: average rectification (clamp)

Ground Voltage: Average Rectification(between S-ES interface)

Test voltage waveform

Sine wave

Test frequency

128Hz

Short circuit test current

AC 20mA max

Open circuit test voltage

AC 28V max

Electrode spacing range

1m¡«100m

Display mode

4-bit large LCD display, with backlight

Measurement instructions

LED flashing indicator during measurement

 

LCD size

111mm¡Á68mm

LCD display field

108mm¡Á65mm

Instrument size

L/W/H£º277.2mm¡Á227.5mm¡Á153mm

Clamp size

L/T/H£º101mm¡Á27mm¡Á214mm

Test line

4 strips£ºred 15m£¬black 15m, yellow 10m£¬green 10m each one

Simple test line

2strips£ºyellow 1.5m£¬green 1.5m each one

Auxiliary Grounding rod

4PCS£º¦Õ10mm¡Á200mm

Current clamp

2PCS£ºBanana plug

Current clamp diameter

¦Õ50mm

Current clamp lead

 Length 2m

Measure time

AC current£ºabout 2 times/sec;

Ground voltage£ºabout 2 times/sec;

grounding resistance¡¢soil resistivity: about 7 seconds/time

Line voltage

Measurement below AC100V (ground voltage measurement function cannot be used to measure commercial power)

USB interface

With USB interface, storage data can be uploaded to the computer, save and print

Communication Line

One USB communication line, 1.5m long

Data storage

500 groups, "MEM" storage indicates, flashing "FULL" symbol indicates that the memory is full

Data review

Data review function: "MR" symbol display

Overflow display

Over-range overflow function: "OL" symbol display

Current clamp low current indication

When measuring by the selection method or the double-clamp method, when the current signal received by the current clamp A is lower than 0.5 mA, the symbol ¡°    ¡± is displayed, and at this time, the clamping direction of the current clamp A should be checked.

Interference test

Automatic identification of interference signals, "NOISE" symbol indication when the interference voltage is higher than 5V

Auxiliary grounding test

With auxiliary ground resistance test function, 0.00K¦¸ ~ 30k¦¸ (Rh max = 3k¦¸ +100R <50k¦¸; Rs max = 3k¦¸ +100R <50k¦¸)

Alarm function

Alarm when the measured value exceeds the alarm setting value

Battery voltage

Real-time display of battery power, reminding timely charging when battery voltage is low

Automatic Shutdown

¡°APO¡± Indicates, automatic Shutdown After 15 Minutes

Power consumption

Standby: 40mA Max(Backlight off)

Turn on backlight: 43mA Max

measuring£º120mA Max(Backlight off)

Weight

Instrument£º 2430g(with battery)

Current clamp£º940g(2PCS)

Test lines£º1300g(including simple test line)

Auxiliary grounding rod£º 850g(4PCS)

Working temperature and humidity

-10¡æ¡«40¡æ£»below 80%rh

Storage temperature and humidity

-20¡æ¡«60¡æ£»below 70%rh

Overload protection

Grounding resistance£ºAC 280V/3 seconds between H-E and S-ES ports

Insulation resistance

20M¦¸ÒÔÉÏ(500V between circuit and housing)

Pressure resistance

AC 3700V/rms(between circuit and housing)

Electromagnetic properties

IEC61326(EMC)

Suitable for safety regulations

IEC61010-1(CAT ¢ó 300V¡¢CAT IV 150V¡¢pollution level 2)£»

IEC61010-031£»

IEC61557-1(grounding resistance)£»

IEC61557-5(soil resistivity)£»

JJG 366-2004.

JJG 366-2004(ground resistance meter)£»

JJG 1054-2009(Clamp grounding resistance meter).