Home >> Product >>Ground Resistance Tester >> ES3030 Digital large ground network tester
Product Detail

ES3030 Digital large ground network tester

    ES3030 digital large-scale grounding grounding resistance tester, also known as power frequency grounding resistance tester, grounding resistance meter, etc. are common instruments for testing and measuring common grounding resistance meters.It adopts new variable frequency AC power supply, dual frequency measurement technology, large touch color screen and microprocessor technology to meet the requirements of two-wire, three-wire and four-wire test impedance. It can also measure soil resistivity, step voltage, distribution potential and contact voltage. , current phase angle and other parameters.Applicable to telecommunications, electric power, meteorology, computer room, oil field, power distribution line, iron tower transmission line, gas station, factory grounding grid, lightning rod, etc., in line with the standards of power substation and lightning protection equipment testing instruments. The instrument test is accurate, fast, simple, stable and reliable.

    ES3030 digital large Grounding Resistance Tester maximum open circuit output voltage up to 400V, the maximum short-circuit current up to 5A.The microprocessor control and automatic dual-frequency technology can accurately measure and calculate the grounding impedance value under the 50Hz power frequency state under  strong interference state, and the large screen display is clear at a glance.It can store 100 sets of data at the same time, and the resistance measurement range is 0.000¦¸¡«2000¦¸. Measurement data can be printed out via a thermal printer..

    ES3030 digital large Grounding Resistance Tester consists of a host computer, test leads, and grounding rods. It has functions such as reading, reviewing, saving, and printing historical data.


Collect
Product Model ES3030
Product Introduction

Function

Ground resistance measurement, soil resistivity measurement, step voltage measurement, distributed potential measurement, contact voltage measurement

Ground resistance range

0.030~2.000¦¸    Accuracy£º¡À2%rdg¡À5dgt

0~20.00¦¸        Accuracy£º¡À2%rdg¡À5dgt

0~200.0¦¸        Accuracy£º¡À2%rdg¡À5dgt

0~2000¦¸        Accuracy£º¡À2%rdg¡À5dgt

Ground resistance resolution

0.001¦¸

Rated measuring power

2000W

Capacity of resisting disturbance

Anti-power frequency 50hz voltage 50v

Base condition

23¡æ¡À5¡æ£¬below 70%rh   (Auxiliary ground resistance 20¦¸¡À10%£¬voltage to earth£¼10V)

Power

AC 220V 10A (50Hz)

Backlight

Controllable gray screen backlight

Measurement mode

four-wire measurement, three-wire measurement, two-wire measurement

Measurement method

Grounding resistance: rated current method

Short circuit test current

1A¡¢2A¡¢3A¡¢4A¡¢5A(5 file settings)

Soil resistivity electrode spacing range

Can set 1m¡«100m

Test frequency

45Hz¡¢55Hz¡¢Automatic dual frequency optional

Short circuit maximum current

AC  5A¡À10%  Sine wave

No-load maximum voltage

AC  400V¡À10%  Sine wave

Display mode

7-inch touch-control color screen

Touch screen

yes

Measurement indication

Measurement progress display, measurement prompt animation display

Instrument size

L/W/H£º540mm*440mm*210mm

Standard test line length

Red 15m£¬black 15m£¬yellow 10m£¬green 10m£¬yellow 1.5m£¬green 1.5m each one

Auxiliary grounding rob

800mm 2pcs , 200mm 2pcs

Measurement time

ground impedance£ºabout 1min/time

Print

Built-in thermal printer

Print paper specification

57*40mm

Data storage

100 groups, "Save successfully!" Store indication, display "Save failed, space is full!" character indicates that the storage is full

Data review

yes

Overflow display

Over-range overflow function: "OL" symbol display

Automatic shut-down

no

Power consumption

Standby: <110W

Measure£º2000W

Weight

Instrument£º27kg

Test line¡¢Auxiliary ground rob¡¢ Instrument bag£º5.5kg

Working temperature and humidity

-10¡æ¡«40¡æ£»Below 80%rh

Storage temperature and humidity

-20¡æ¡«60¡æ£»Below 70%rh

Insulation resistance

10M¦¸ above(Between circuit and case500V)

Pressure resistance

AC 3700V/rms(Between circuit and case)

Electromagnetic properties

IEC61010-4-3£¬Wireless frequency electromagnetic field¡Ü1V/m

Suitable for Safety Regulations

IEC61010-1¡¢IEC1010-2-31¡¢IEC61557-1,5¡¢IEC60529(IP54)¡¢Pollution Degree 2¡¢CAT ¢ó 300V