Home >> Product >>Other Tester >> FR2060 non-contact phase sequence table
Product Detail

FR2060 non-contact phase sequence table

    The FR2060 non-contact phase detector is a major breakthrough in the traditional phase sequence detection method. The traditional phase sequence detection is that the terminal of the three-phase wire must be disconnected, and the three exposed clamps or test pins of the phase sequence meter must be connected to the three exposed live wires. The FR2060 adopts the clamp non-contact inductive measurement, which does not need to open the wire and contact the high-voltage exposed live wire, The phase sequence can be detected by directly clamping three ultra-induction high insulation clamps on the insulation sheath of the three-phase live wire, and the sound and light indicate the positive or reverse phase status of the phase sequence of the three-phase power supply.

    FR2060 non-contact phase detector has the functions of live line inspection, simple power inspection, open circuit finding, breakpoint location, line maintenance, etc.

The FR2060 non-contact phase detector is fast and convenient to detect, and the display is clear at a glance, which greatly improves the safety of on-site testing, effectively protects the personal safety of operators, and increases productivity! It is a safety regulation instrument for three-phase power phase sequence, motor detection and line maintenance!


Collect
Product Model FR2060
Product Introduction

Function

Phase detection (positive phase, reverse phase), live line inspection, simple electricity inspection, phase loss judgment, circuit breaker search, break point location, and line maintenance.

Power

9V battery, continuous use time is about 70 hours.

Measure mode

Non-contact clipping method

Wire position

The measured wire is in the center of the jaw

Frequency

50Hz/60Hz Automatic Identification

Live electricity range

AC70¡«1000V£¬45/65Hz£¨Sine wave continuous input£©£¬Conducted electrostatic detection

Measuring the highest voltage

AC1000V

Clamp wire size

Outside diameter ø1.5mm¡«ø48mm

Display

¡¾Positive phase¡¿4 phase detector lights are turned on in a clockwise direction£»

¡¾Reverse phase¡¿4 4 phase detection lights are turned on counterclockwise;

¡¾Live electricity¡¿L1, L2, L3 lights in the voltage setting range£»

¡¾Lack of phase¡¿L1 or L2 or L3 lights are not lit£»

¡¾Open circuit¡¿L1 or L2 or L3 lights are not lit

Beep

¡¾Positive phase¡¿The instrument emits intermittent short beep£»

¡¾Reverse phase¡¿The instrument emits a continuous long beep¡£

Battery check

After the power is turned on, the POWER indicator is on; the battery is low; the LOW BATTERY lamp is on¡£

Clamp lead length

0.6m

Instrument size

L 117.6mm¡ÁW 81mm¡ÁT 25mm

Automatic shut-down

After about 6 minutes of power on, the meter automatically shuts down to reduce battery consumption.

Battery voltage

When the battery voltage drops to about 5.2V, the battery voltage is low symbol to remind to replace the battery

Instrument weight

Instrument£º260g(including battery)

Maximum rated power

300mVA

Working temperature and humidity

-10¡æ¡«55¡æ£»below 80%rh

Storage temperature and humidity

-20¡æ¡«60¡æ£»below 90%rh

Insulation strength

3.7kVrms

Suitable for Safety Regulations

EN61010-1£º2001¡¢EN61010-031£º2002¡¢pollution grade 2¡¢CAT ¢ó(600V)¡¢Instant overvoltage 6000V¡£